
Macro-Tech 600/1200/2400 Power Amplifiers
Page 10
If the air supply is unusually dusty, you might want to
pre-filter it using commercial furnace filters to prevent
rapid loading of the unit’s own air filter. When needed,
the unit’s filter can be cleaned with mild dish detergent
and water (see Section 4.5).
BLOWER
(OPTION 2)
BLOWER
(OPTION 1)
AIR
FLOW
FRONT
OF
RACK
DOOR
AIR
FLOW
EQUIPMENT
RACK
(SIDE VIEW)
Fig. 3.3 Proper Air Flow in a Rack Cabinet
3 Installation
3.1 Mounting
Macro-Tech
amplifiers are designed for standard
19-inch (48.3 cm) rack mounting and “stack” mount-
ing without a cabinet. For more efficient cooling and
extra support in a rack, it is recommended that units
be stacked directly on top of each other.
Important: If the unit will be transported, it should also
be securely supported at the back of the rack.
Fig. 3.2 Top View of a Rack-Mounted Unit
AIR
FLOW
AIR FLOW
AMPLIFIER
(TOP VIEW)
RACK
CABINET
16 in
40.6 cm
2 in
(5 cm)
MIN.
IMPORTANT: Be sure rear of amplifier
is securely mounted to rack.
17 in
43.2 cm
AIR
FLOW
3.2 Cooling
NEVER block the side or front air vents.
Macro-Tech
amplifiers do not need to be mounted with space be-
tween them. If you must leave open spaces in a rack
for any reason, close them with blank panels to pre-
vent air from recycling into the front of other ampliers.
Allow at least 35 cubic feet (1 cubic meter) per minute
per unit for the
Macro-Tech 600
and
1200
, and at least
45 cubic feet (1.3 cubic meters) per minute per unit for
the
Macro-Tech 2400
. Additional air flow may be re-
quired when driving low impedance loads at consis-
tently high output levels. Refer to Section 7 for detailed
information on thermal dissipation.
Fig. 3.1 Mounting Dimensions
19 in
48.3 cm
16 in
40.6 cm
3.5 in
8.9 cm
2.5 in
6.35 cm
SIDE VIEW
LEVEL LEVEL
ON
OFF
30
27
24
21
18
15
12
9
6
3
0
ENABLECH1 CH2
ODEP
30
27
24
21
9
6
3
0
SIGNAL
/
IOC
18
15
12
When mounting the amplifier in a rack, the side walls of
the rack should be at least 2 inches (5 cm) away from
the chassis as shown in Figure 3.2.
Tip:
An easy way to verify adequate cooling is to ob-
serve the ODEP indicators while the amplifier is oper-
ating under worst-case conditions. If the indicators
dim, additional cooling is recommended.
If your rack has a front door that could block air flow to
the amplifier’s air intakes, you must provide adequate
air flow by installing a grille in the door or by pressuriz-
ing the air behind the door. Wire grilles are recom-
mended over perforated panels because they tend to
cause less air restriction. A good choice for pressuriz-
ing the air behind a rack cabinet door is to mount a
“squirrel cage” blower inside the rack (Option 1 be-
low). At the bottom of the rack, mount the blower so it
blows outside air into the space between the door and
in front of the amplifiers, pressurizing the “chimney”
behind the door. This blower should not blow air into or
take air out of the space behind the amplifiers. For
racks without a door, you can evacuate the rack by
mounting the blower at the top of the rack so that air
inside the cabinet is drawn out the back (Option 2 be-
low).
Kommentare zu diesen Handbüchern